Code of Ethics

AHI Code of Ethics
The following rules of conduct and ethics help maintain integrity and
objectivity within the home inspection profession. In any instance where the
AHI Code of Ethics and the law conflict, the obligations of the law shall
take precedence.
I. PROFESSIONAL CONDUCT
The home inspector shall

  1. Always act in good faith when dealing with a client.
  2. Not disclose the results of a home inspection to any other party
    without client approval.
  3. Not express an opinion unless it is based on fact, education, or
    experience.
  4. Not accept compensation from more than one interested party for the
    same service without the consent of all interested parties.
  5. Not accept commissions or allowances from other parties involved
    with the real estate transaction.
  6. Maintain truth in advertising, marketing, and promotion of services or
    qualifications.
  7. Not advise a client whether or not to buy a property after the home
    inspection.
  8. Immediately disclose any observed immediate safety hazards to
    occupants exposed to such hazards.
  9. Comply with any inquiry or compliance requirement by a home
    inspector regulatory body.
  10. Not aid or assist another in the violation of this Code of Ethics.
    II. THE INSPECTION AND REPORT
    The home inspector shall
  11. Perform an inspection that is substantially in compliance with the AHI
    Standards of Practice.
  12. Enter into a written agreement with the client prior to the inspection
    that includes the scope of the home inspection, listing the components
    and systems to be inspected along with limitations and exclusions.
  13. Inspect all items that fall within the scope of the home inspection
  14. Submit a written report to the client within 1-2 business days that
    a. describes inspected systems and components;
    b. reports any items deemed significantly deficient;
    c. states why items were deemed significantly deficient;
    d. discloses items within the scope that were not inspected and the reason.
    III. DISCLOSURE OF A CONFLICT OF INTEREST
    The home inspector shall
  15. Prior to the inspection, disclose in writing to the client any personal
    interests that may affect the client;
  16. Not allow any personal interest to affect the quality of the results of a
    home inspection;
  17. Provide additional services to the client only after securing the written
    consent of the client in a separate agreement that includes a written
    statement of the services intended and how such additional services
    may conflict with the home inspection services provided.

Standards of Practice:

I)The Home Inspection: is based on the observations made on the date of the
inspection, and not a prediction of future conditions.
II. The home inspection will not reveal every issue that exists or ever could exist, but
only those material defects observed on the date of the inspection.
1.2. A material defect is a specific issue with a system or component of a residential
property that may have a significant, adverse impact on the value of the property, or that
poses an unreasonable risk to people. The fact that a system or component is near, at,
or beyond the end of its normal, useful life is not, in itself, a material defect.
1.3. A home inspection report shall identify, in written format, defects within
specific systems and components defined by these Standards that are both observed and
deemed material by the inspector. Inspection reports may include additional comments
and recommendations.
2) Limitations, Exceptions & Exclusions
2.1. Limitations:
I. An inspection is not technically exhaustive.
II. An inspection will not identify concealed or latent defects, “vices cachees”
III. An inspection will not deal with aesthetic concerns, or what could be deemed
matters of taste, cosmetic defects, etc.
IV. An inspection will not determine the suitability of the property for any use.
V. An inspection does not determine the market value of the property or its
marketability.
VI. An inspection does not determine the insurability of the property.
VII. An inspection does not determine the advisability or inadvisability of the
purchase of the inspected property.
VIII. An inspection does not determine the life expectancy of the property or any
components or systems therein.
IX. An inspection does not include items not permanently installed.
X. This Standards of Practice applies to properties with four or fewer residential
units and their attached garages and carports.
2.2. Exclusions:
I. The inspector is not required to determine:
A. property boundary lines or encroachments.
B. the condition of any component or system that is not readily accessible.
C. the service life expectancy of any component or system.
D. the size, capacity, BTU, performance or efficiency of any component or
system.
E. the cause or reason of any condition.
F. the cause for the need of correction, repair or replacement of any system or
component.
G. future conditions.

H. compliance with codes or regulations.
I. the presence of evidence of rodents, birds, bats, animals, insects, or other
pests.
J. the presence of mold, mildew or fungus.
K. the presence of airborne hazards, including radon.
L. the air quality.
M. the existence of environmental hazards, including lead paint, asbestos or toxic
drywall.
N. the existence of electromagnetic fields.
O. any hazardous waste conditions.
P. any manufacturers’ recalls or conformance with manufacturer installation, or
any information included for consumer protection purposes.
Q. acoustical properties.
R. correction, replacement or repair cost estimates.
S. estimates of the cost to operate any given system.
II. The inspector is not required to operate:
A. any system that is shut down.
B. any system that does not function properly.
C. or evaluate low-voltage electrical systems, such as, but not limited to:

  1. phone lines;
  2. cable lines;
  3. satellite dishes;
  4. antennae;
  5. lights; or
  6. remote controls.
    D. any system that does not turn on with the use of normal operating controls.
    E. any shut-off valves or manual stop valves.
    F. any electrical disconnect or over-current protection devices.
    G. any alarm systems.
    H. moisture meters, gas detectors or similar equipment.
    III. The inspector is not required to:
    A. move any personal items or other obstructions, such as, but not limited
    to: throw rugs, carpeting, wall coverings, furniture, ceiling tiles, window
    coverings, equipment, plants, ice, debris, snow, water, dirt, pets, or anything
    else that might restrict the visual inspection.
    B. dismantle, open or uncover any system or component.
    C. enter or access any area that may, in the inspector’s opinion, be unsafe.
    D. enter crawlspaces or other areas that may be unsafe or not readily accessible.
    E. inspect underground items, such as, but not limited to: lawn-irrigation
    systems, or underground storage tanks (or indications of their presence),
    whether abandoned or actively used.
    F. do anything that may, in the inspector’s opinion, be unsafe or dangerous to
    him/herself or others, or damage property, such as, but not limited
    to: walking on roof surfaces, climbing ladders, entering attic spaces, or
    negotiating with pets.
    G. inspect decorative items.
    H. inspect common elements or areas in multi-unit housing.
    I. inspect intercoms, speaker systems or security systems.
    J. offer guarantees or warranties.
    K. offer or perform any engineering services.
    L. offer or perform any trade or professional service other than a home
    inspection.
    M. research the history of the property, or report on its potential for alteration,
    modification, extendibility or suitability for a specific or proposed use for
    occupancy.
    N. determine the age of construction or installation of any system, structure or
    component of a building, or differentiate between original construction and
    subsequent additions, improvements, renovations or replacements.
    O. determine the insurability of a property.
    P. perform or offer Phase 1 or environmental audits.
    Q. inspect any system or component that is not included in these Standards.
    3)Standards of Practice
    3.1. Roof
    I. The inspector shall inspect from ground level or the eaves:
    A. the roof-covering materials;
    B. the gutters;
    C. the downspouts;
    D. the vents, flashing, skylights, chimney, and other roof penetrations; and
    E. the general structure of the roof from the readily accessible panels, doors or
    stairs.
    II. The inspector shall describe:
    A. the type of roof-covering materials.
    III. The inspector shall report as in need of correction:
    A. observed indications of active roof leaks.
    IV. The inspector is not required to:
    A. walk on any roof surface.
    B. predict the service life expectancy.
    C. inspect underground downspout diverter drainage pipes.
    D. remove snow, ice, debris or other conditions that prohibit the observation of
    the roof surfaces.
    E. move insulation.
    F. inspect antennae, satellite dishes, lightning arresters, de-icing equipment, or
    similar attachments.
    G. walk on any roof areas that appear, in the inspector’s opinion, to be unsafe.
    H. walk on any roof areas if doing so might, in the inspector’s opinion, cause
    damage.
    I. perform a water test.
    J. warrant or certify the roof.
    K. confirm proper fastening or installation of any roof-covering material.
    3.2. Exterior
    I. The inspector shall inspect:
    A. the exterior wall-covering materials;
    B. the eaves, soffits and fascia;
    C. a representative number of windows;
    D. all exterior doors;
    E. flashing and trim;
    F. adjacent walkways and driveways;
    G. stairs, steps, stoops, stairways and ramps;
    H. porches, patios, decks, balconies and carports;
    I. railings, guards and handrails; and
    J. vegetation, surface drainage, retaining walls and grading of the property,
    where they may adversely affect the structure due to moisture intrusion.
    II. The inspector shall describe:
    A. the type of exterior wall-covering materials.
    III. The inspector shall report as in need of correction:
    A. any improper spacing between intermediate balusters, spindles and rails.
    IV. The inspector is not required to:
    A. inspect or operate screens, storm windows, shutters, awnings, fences,
    outbuildings, or exterior accent lighting.
    B. inspect items that are not visible or readily accessible from the ground,
    including window and door flashing.
    C. inspect or identify geological, geotechnical, hydrological or soil conditions.
    D. inspect recreational facilities or playground equipment.
    E. inspect seawalls, breakwalls or docks.
    F. inspect erosion-control or earth-stabilization measures.
    G. inspect for safety-type glass.
    H. inspect underground utilities.
    I. inspect underground items.

    J. inspect wells or springs.
    K. inspect solar, wind or geothermal systems.
    L. inspect swimming pools or spas.
    M. inspect wastewater treatment systems, septic systems or cesspools.
    N. inspect irrigation or sprinkler systems.
    O. inspect drainfields or dry wells.
    P. determine the integrity of multiple-pane window glazing or thermal window
    seals.
    3.3. Basement, Foundation, Crawlspace & Structure
    I. The inspector shall inspect:
    A. the foundation;
    B. the basement;
    C. the crawlspace; and
    D. structural components.
    II. The inspector shall describe:
    A. the type of foundation; and
    B. the location of the access to the under-floor space.
    III. The inspector shall report as in need of correction:
    A. observed indications of wood in contact with or near soil;
    B. observed indications of active water penetration;
    C. observed indications of possible foundation movement, such as sheetrock
    cracks, brick cracks, out-of-square door frames, and unlevel floors; and
    D. any observed cutting, notching and boring of framing members that may, in
    the inspector’s opinion, present a structural or safety concern.
    IV. The inspector is not required to:
    A. enter any crawlspace that is not readily accessible, or where entry could cause
    damage or pose a hazard to him/herself.
    B. move stored items or debris.
    C. operate sump pumps with inaccessible floats.
    D. identify the size, spacing, span or location or determine the adequacy of
    foundation bolting, bracing, joists, joist spans or support systems.
    E. provide any engineering or architectural service.
    F. report on the adequacy of any structural system or component.
    3.4. Heating
    I. The inspector shall inspect:
    A. the heating system, using normal operating controls.
    II. The inspector shall describe:
    A. the location of the thermostat for the heating system;
    B. the energy source; and
    C. the heating method.
    III. The inspector shall report as in need of correction:
    A. any heating system that did not operate; and
    B. if the heating system was deemed inaccessible.
    IV. The inspector is not required to:
    A. inspect, measure, or evaluate the interior of flues or chimneys, fire chambers,
    heat exchangers, combustion air systems, fresh-air intakes, makeup air,
    humidifiers, dehumidifiers, electronic air filters, geothermal systems, or solar
    heating systems.
    B. inspect fuel tanks or underground or concealed fuel supply systems.
    C. determine the uniformity, temperature, flow, balance, distribution, size,
    capacity, BTU, or supply adequacy of the heating system.
    D. light or ignite pilot flames.
    E. activate heating, heat pump systems, or other heating systems when ambient
    temperatures or other circumstances are not conducive to safe operation or
    may damage the equipment.
    F. override electronic thermostats.
    G. evaluate fuel quality.
    H. verify thermostat calibration, heat anticipation, or automatic setbacks, timers,
    programs or clocks.
    I. measure or calculate the air for combustion, ventilation, or dilution of flue
    gases for appliances.
    3.5. Cooling
    I. The inspector shall inspect:
    A. the cooling system, using normal operating controls.
    II. The inspector shall describe:
    A. the location of the thermostat for the cooling system; and
    B. the cooling method.
    III. The inspector shall report as in need of correction:
    A. any cooling system that did not operate; and
    B. if the cooling system was deemed inaccessible.
    IV. The inspector is not required to:
    A. determine the uniformity, temperature, flow, balance, distribution, size,
    capacity, BTU, or supply adequacy of the cooling system.
    B. inspect portable window units, through-wall units, or electronic air filters.
    C. operate equipment or systems if the exterior temperature is below 65°
    Fahrenheit, or when other circumstances are not conducive to safe operation
    or may damage the equipment.
    D. inspect or determine thermostat calibration, cooling anticipation, or automatic
    setbacks or clocks.
    E. examine electrical current, coolant fluids or gases, or coolant leakage.
    3.6. Plumbing
    I. The inspector shall inspect:
    A. the main water supply shut-off valve;
    B. the main fuel supply shut-off valve;
    C. the water heating equipment, including the energy source, venting
    connections, temperature/pressure-relief (TPR) valves, Watts 210 valves, and
    seismic bracing;
    D. interior water supply, including all fixtures and faucets, by running the water;
    E. all toilets for proper operation by flushing;
    F. all sinks, tubs and showers for functional drainage;
    G. the drain, waste and vent system; and
    H. drainage sump pumps with accessible floats.
    II. The inspector shall describe:
    A. whether the water supply is public or private based upon observed evidence;
    B. the location of the main water supply shut-off valve;
    C. the location of the main fuel supply shut-off valve;
    D. the location of any observed fuel-storage system; and
    E. the capacity of the water heating equipment, if labeled.
    III. The inspector shall report as in need of correction:
    A. deficiencies in the water supply by viewing the functional flow in two fixtures
    operated simultaneously;
    B. deficiencies in the installation of hot and cold water faucets;
    C. active plumbing water leaks that were observed during the inspection; and
    D. toilets that were damaged, had loose connections to the floor, were leaking, or
    had tank components that did not operate.
    IV. The inspector is not required to:
    A. light or ignite pilot flames.
    B. measure the capacity, temperature, age, life expectancy or adequacy of the
    water heater.
    C. inspect the interior of flues or chimneys, combustion air systems, water
    softener or filtering systems, well pumps or tanks, safety or shut-off valves,
    floor drains, lawn sprinkler systems, or fire sprinkler systems.
    D. determine the exact flow rate, volume, pressure, temperature or adequacy of
    the water supply.
    E. determine the water quality, potability or reliability of the water supply or
    source.
    F. open sealed plumbing access panels.
    G. inspect clothes washing machines or their connections.
    H. operate any valve.
    I. test shower pans, tub and shower surrounds or enclosures for leakage or for
    functional overflow protection.
    J. evaluate the compliance with conservation, energy or building standards, or
    the proper design or sizing of any water, waste or venting components, fixtures
    or piping.
    K. determine the effectiveness of anti-siphon, back-flow prevention or drain-stop
    devices.
    L. determine whether there are sufficient cleanouts for effective cleaning of
    drains.
    M. evaluate fuel storage tanks or supply systems.
    N. inspect wastewater treatment systems.

    O. inspect water treatment systems or water filters.
    P. inspect water storage tanks, pressure pumps, or bladder tanks.
    Q. evaluate wait time to obtain hot water at fixtures, or perform testing of any
    kind to water heater elements.
    R. evaluate or determine the adequacy of combustion air.
    S. test, operate, open or close: safety controls, manual stop valves,
    temperature/pressure-relief valves, control valves, or check valves.
    T. examine ancillary or auxiliary systems or components, such as, but not limited
    to, those related to solar water heating and hot water circulation.
    U. determine the existence or condition of polybutylene, polyethylene, or similar
    plastic piping.
    V. inspect or test for gas or fuel leaks, or indications thereof.
    3.7. Electrical
    I. The inspector shall inspect:
    A. the service drop;
    B. the overhead service conductors and attachment point;
    C. the service head, gooseneck and drip loops;
    D. the service mast, service conduit and raceway;
    E. the electric meter and base;
    F. service-entrance conductors;
    G. the main service disconnect;
    H. panelboards and over-current protection devices (circuit breakers and fuses);
    I. service grounding and bonding;
    J. a representative number of switches, lighting fixtures and receptacles,
    including receptacles observed and deemed to be arc-fault circuit interrupter
    (AFCI)-protected using the AFCI test button, where possible;
    K. all ground-fault circuit interrupter receptacles and circuit breakers observed
    and deemed to be GFCIs using a GFCI tester, where possible; and
    L. for the presence of smoke and carbon monoxide detectors.
    II. The inspector shall describe:
    A. the main service disconnect’s amperage rating, if labeled; and
    B. the type of wiring observed.
    III. The inspector shall report as in need of correction:
    A. deficiencies in the integrity of the service-entrance conductors’ insulation, drip
    loop, and vertical clearances from grade and roofs;
    B. any unused circuit-breaker panel opening that was not filled;
    C. the presence of solid conductor aluminum branch-circuit wiring, if readily
    visible;
    D. any tested receptacle in which power was not present, polarity was incorrect,
    the cover was not in place, the GFCI devices were not properly installed or did
    not operate properly, evidence of arcing or excessive heat, and where the
    receptacle was not grounded or was not secured to the wall; and
    E. the absence of smoke and/or carbon monoxide detectors.
    IV. The inspector is not required to:
    A. insert any tool, probe or device into the main panelboard, sub-panels,
    distribution panelboards, or electrical fixtures.
    B. operate electrical systems that are shut down.
    C. remove panelboard cabinet covers or dead fronts.
    D. operate or re-set over-current protection devices or overload devices.
    E. operate or test smoke or carbon monoxide detectors or alarms.
    F. inspect, operate or test any security, fire or alarm systems or components, or
    other warning or signaling systems.
    G. measure or determine the amperage or voltage of the main service
    equipment, if not visibly labeled.
    H. inspect ancillary wiring or remote-control devices.
    I. activate any electrical systems or branch circuits that are not energized.
    J. inspect low-voltage systems, electrical de-icing tapes, swimming pool wiring,
    or any time-controlled devices.
    K. verify the service ground.
    L. inspect private or emergency electrical supply sources, including, but not
    limited to: generators, windmills, photovoltaic solar collectors, or battery or
    electrical storage facility.
    M. inspect spark or lightning arrestors.
    N. inspect or test de-icing equipment.
    O. conduct voltage-drop calculations.
    P. determine the accuracy of labeling.
    Q. inspect exterior lighting.
    3.8. Fireplace
    I. The inspector shall inspect:
    A. readily accessible and visible portions of the fireplaces and chimneys;
    B. lintels above the fireplace openings;
    C. damper doors by opening and closing them, if readily accessible and manually
    operable; and
    D. cleanout doors and frames.
    II. The inspector shall describe:
    A. the type of fireplace.
    III. The inspector shall report as in need of correction:
    A. evidence of joint separation, damage or deterioration of the hearth, hearth
    extension or chambers;
    B. manually operated dampers that did not open and close;
    C. the lack of a smoke detector in the same room as the fireplace;
    D. the lack of a carbon monoxide detector in the same room as the fireplace; and
    E. cleanouts not made of metal, pre-cast cement, or other non-combustible
    material.
    IV. The inspector is not required to:
    A. inspect the flue or vent system.
    B. inspect the interior of chimneys or flues, fire doors or screens, seals or gaskets,
    or mantels.
    C. determine the need for a chimney sweep.
    D. operate gas fireplace inserts.
    E. light pilot flames.
    F. determine the appropriateness of any installation.
    G. inspect automatic fuel-fed devices.
    H. inspect combustion and/or make-up air devices.
    I. inspect heat-distribution assists, whether gravity-controlled or fan-assisted.
    J. ignite or extinguish fires.
    K. determine the adequacy of drafts or draft characteristics.
    L. move fireplace inserts, stoves or firebox contents.
    M. perform a smoke test.
    N. dismantle or remove any component.
    O. perform a National Fire Protection Association (NFPA)-style inspection.
    P. perform a Phase I fireplace and chimney inspection.
    3.9. Attic, Insulation & Ventilation
    I. The inspector shall inspect:
    A. insulation in unfinished spaces, including attics, crawlspaces and foundation
    areas;
    B. ventilation of unfinished spaces, including attics, crawlspaces and foundation
    areas; and
    C. mechanical exhaust systems in the kitchen, bathrooms and laundry area.
    II. The inspector shall describe:
    A. the type of insulation observed; and
    B. the approximate average depth of insulation observed at the unfinished attic
    floor area or roof structure.
    III. The inspector shall report as in need of correction:
    A. the general absence of insulation or ventilation in unfinished spaces.
    IV. The inspector is not required to:
    A. enter the attic or any unfinished spaces that are not readily accessible, or
    where entry could cause damage or, in the inspector’s opinion, pose a safety
    hazard.
    B. move, touch or disturb insulation.
    C. move, touch or disturb vapor retarders.
    D. break or otherwise damage the surface finish or weather seal on or around
    access panels or covers.
    E. identify the composition or R-value of insulation material.
    F. activate thermostatically operated fans.
    G. determine the types of materials used in insulation or wrapping of pipes,
    ducts, jackets, boilers or wiring.
    H. determine the adequacy of ventilation.
    3.10. Doors, Windows & Interior
    I. The inspector shall inspect:
    A. a representative number of doors and windows by opening and closing them;
    B. floors, walls and ceilings;
    C. stairs, steps, landings, stairways and ramps;

    D. railings, guards and handrails; and
    E. garage vehicle doors and the operation of garage vehicle door openers, using
    normal operating controls.
    II. The inspector shall describe:
    A. a garage vehicle door as manually-operated or installed with a garage door opener.
    III. The inspector shall report as in need of correction:
    A. improper spacing between intermediate balusters, spindles and rails for steps,
    stairways, guards and railings;
    B. photo-electric safety sensors that did not operate properly; and
    C. any window that was obviously fogged or displayed other evidence of broken
    seals.
    IV. The inspector is not required to:
    A. inspect paint, wallpaper, window treatments or finish treatments.
    B. inspect floor coverings or carpeting.
    C. inspect central vacuum systems.
    D. inspect for safety glazing.
    E. inspect security systems or components.
    F. evaluate the fastening of islands, countertops, cabinets, sink tops or fixtures.
    G. move furniture, stored items, or any coverings, such as carpets or rugs, in
    order to inspect the concealed floor structure.
    H. move suspended-ceiling tiles.
    I. inspect or move any household appliances.
    J. inspect or operate equipment housed in the garage, except as otherwise noted.
    K. verify or certify the proper operation of any pressure-activated auto-reverse or
    related safety feature of a garage door.
    L. operate or evaluate any security bar release and opening mechanisms, whether
    interior or exterior, including their compliance with local, state or federal
    standards.
    M. operate any system, appliance or component that requires the use of special
    keys, codes, combinations or devices.
    N. operate or evaluate self-cleaning oven cycles, tilt guards/latches, or signal
    lights.
    O. inspect microwave ovens or test leakage from microwave ovens.
    P. operate or examine any sauna, steam-generating equipment, kiln, toaster, ice
    maker, coffee maker, can opener, bread warmer, blender, instant hot-water
    dispenser, or other small, ancillary appliances or devices.
    Q. inspect elevators.
    R. inspect remote controls.
    S. inspect appliances.
    T. inspect items not permanently installed.
    U. discover firewall compromises.
    V. inspect pools, spas or fountains.
    W. determine the adequacy of whirlpool or spa jets, water force, or bubble effects.
    X. determine the structural integrity or leakage of pools